LTMR full from , What is LTMR Industrial MCC Penal DOL Star Delta starter - industrial job knowledge

Chemical Plant Interview Related Question & Answer

SUBSCRIBE Us

Wednesday 22 September 2021

LTMR full from , What is LTMR Industrial MCC Penal DOL Star Delta starter

LTMR full from - Low Tension Motor Relay

What is LTMR?


Schneider TeSys T Motor management system

Two hardware components

1 ) LTMR - Main controller

2) LTME - Expansion & Voltage sensing (voltage range 110V - 690V AC)

Application: DOL ,STAR-DELTA, R-DOL AUTO TRANSFORMER,  MOTOR STARTER.


  • The microprocessor-based LTMR controller is the central component in the system that manages the control, protection, and monitoring functions of single-phase or three-phase AC induction motors.

LTMR FUNCTION


1) Motor Metering and Monitoring
2) Motor Protection
3) Motor Control


1) Motor Metering and Monitoring


✓ Easily Measurement - Motor Current, Voltage, Frequency, Power, Power Factor

✓ Monitoring 

  • Fault and warning counters.
  • Motor history.
  • System and device monitoring faults.
  • System operating status.

2)Motor Protection


  • Thermal motor protection with time delay
  • Current motor protection with time delay
  • Voltage and power motor protection with time delay


3) Motor Control

Control channels (local/remote control source selection),Operating modes, Fault management independently start, stop input

LTMR Controller
Functional Description:


  • Current sensing 0.4...100 A
  • Single-phase or three-phase current inputs
  • Six discrete logic inputs
  • Four relay outputs: three SPST, one DPST
  • Connections for a ground current sensor
  • Connection for a motor temperature sensor
  • Connection for a communication network
  • Connection for HMI device or expansion module
  • Current protection, metering, and monitoring functions
  • Motor control functions
  • Power indicator and communication protocol selection indicator
  • Fault and warning LED indicators
  • Network communication and alarm indicators
  • HMI communication LED indicator
  • Test and reset function

LTME Expansion Module
Functional Description:



  •  Voltage sensing 110...690 Vac, 47...63 Hz
  •  Three-phase voltage inputs
  •  Four additional discrete logic inputs
  •  Additional voltage protection, metering, and monitoring functions
  •  Power LED indicator
  •  Logic input status LED indicators
  •  Additional components required for an optional expansion module:
  •  LTMR controller to LTME connection cable

LTMCUF Control Operator Unit
Functional Description:


  • Configures the system through menu entries
  • Displays parameters, warnings, and faults
  • Controls the motor
  • Provides the FDR (Fast Device Replacement) service (only with LTMCUF with embedded memory)
  • Additional components required for an optional HMI device: LTMR/LTME to HMI communication cable

Magelis XBTN410
Functional Description:

  • Configures the system through menu entries
  • Displays parameters, warnings, and faults
  • Additional components required for an optional HMI device:
  • Separate power source
  • LTMR/LTME to HMI communication cable
  • Magelis XBTL1000 programming software
  • Control channels (local/remote control source selection),Operating modes, Fault management.


LTMR  ELECTRICAL  SPECIFICATION:

Voltage supply for LTMR controller

 Two option: AC or DC

AC 110V-240V 50-60Hz    DC:24V


part number

AC: LTMR_ _FB

DC:LTMR_ _ BD



logic input

Next part coming soon get more details search HERE

Get more details in Video LTMR


 

No comments:

Post a Comment

Interview Question And Answer